How it is worked out
Voltage drop = 2 × K × amps × one-way feet ÷ circular mils. K is 12.9 for copper and 21.2 for aluminum. For three-phase, use 1.732 in place of 2.
A worked example
Fifteen amps over 100 feet of 12 AWG copper: 2 × 12.9 × 15 × 100 ÷ 6,530 is 5.9 volts, about 4.9% of 120.
Good to know
- This does not size a wire. The smallest wire allowed for a circuit is set by the electrical code and the breaker. A wire can pass this sum and still be too small to be safe. Wiring must be done to code by a qualified person.
How we know this calculator is right
Before this calculator went on the site, 4 answers were worked out separately from its code, by hand or straight from the formula above. Each time this page loads, your own browser runs the calculator on those same numbers and compares. Turn on JavaScript to see the comparison.
See every check
| Numbers used | Result | Worked out separately | This calculator |
|---|
What this proves: the calculator does the arithmetic of the formula shown, correctly. What it cannot prove: your measurements, or figures such as coverage per bag, waste and spacing, which are typical starting values you can change. Go by the product label and your local code.